STR2 Hardware Manual
920-0059B
1/30/2014
FAULT Output
e STR2 features a digital FAULT output. is output closes to
signal a fault condition.
is output can be used to drive LEDs, relays and the inputs of
other electronic devices like PLCs. e “+” (collector) and “-” (emier) terminals of the output
transistor are available at the connector. is allows you to congure the output for current
sourcing or sinking.
Diagrams of each type of connection follow.
Do not connect the output to more than 30VDC.
e current through the output terminal must not exceed 80 mA.
Sinking Output
STR2
5-24 VDC
Power Supply
+
Load
OUT-
OUT+
!
STR2
5-24 VDC
Power Supply
+
Load
OUT-
OUT+
Sourcing Output
Driving a Relay
STR2
OUT-
OUT+
1N4935 suppression diode
5-24 VDC
Power Supply
+
relay
FAULT+
FAULT-